Original Article

A Quantitative Noise Survey in a General Room–Based Data Center

Abstract

Acoustic experimental data of IRIB (Islamic Republic of Iran Broadcasting) server room was taken to measure the acoustic noise characteristics of frequency and Sound Pressure Level (SPL). The purposes of this paper are measuring the noise pollution and its evaluation through the regulations. The measurements were taken in two stages. The first one was taken at 10 points by Sound Investigator 2260 using ISO 3741: 1999(E) standard. The results indicate that IRIB server room is an acoustic noise polluted according to Iranian National Building Regulations. Measured data and its frequency analysis show that the high sound energy belongs to low frequencies in the server room. This is confirmed by the next stage of measurement. It was an hour long non-stop noise measurement in the server room to investigate noise exposure level by customers and employees. The Equivalent instant noise level on Aweighting network was 75 dBA. The results are valid for all of data centres, although this study is involved with a special case study. Two main factors are important in server room noise pollution scenario; the amount of sound absorbance in the space and environmental noise characteristics. Most surfaces in server rooms are hard and have low absorbance coefficient, therefore, the intensity of travelling sound increases. On the other hand, the main noise sources in any server room are fans which work usually on a narrowband with a fundamental frequency. So as the main features of server room acoustic noise are the same, the presented results can be generalized to any server room.

Nasiri P. Noise Pollution. In: Textbook of Public Health. published by Iran Ministry of Health and Medical Education, 2012; p.342; Available from: http://www.elib.hbi.ir/persian/PUBLIC_HEALTH_EBOOK/04_06.htm

Dunlap K, Rasmussen N. Choosing between Room, Row, and Rack-based Cooling for Data Centers. APC UK Co. 2014. Available from: http://www.ithound.com/abstract/choosing-row-rack-cooling-centers-19884.

Price DL, De Wilde JP, Papadaki AM, Curran JS, Kitney RI. Investigation of acoustic noise on 15 MRI scanners from 0.2 T to 3 T. J Magn Reson Imaging 2001; 13(2): 288-93.

Brigham Young University. Acoustical Analysis of Active Control in the Server Room of a C7 Data Centers Colocation Facility. Feasibility Report. June 2010.

ISO. Acoustics- Determination of Sound Power Levels of noise sources using sound pressure – precision methods for reverberation rooms. International Standard Organization ISO 3741. 1999.

Leo L.Beranek. Revised Criteria for noise in building. Noise Control 1957; 3(1).

Recommended Noise Criterion. Available from: http://www.engineeringtoolbox.com/nc-noise-criterion-d_725.html.

B&K. 2260 INVESTIGATOR. Brüel & Kjær manufacture Report.

Online Noise Criteria (NC) Calculator. Available from: http://www.engineeringtoolbox.com/nc-noise-criterion-d_517.html.

Daniel R.R. The SCIENCE and APPLICATIONS of ACOUSTICS. 2nd ed, Springer publishing Co., New York, 2006.

MATLAB R2009a help. The Mathworks, Inc., 2009.

Hemond C.J. Engineering Acoustics and Noise Control. 1st ed, Prentice Hall publishing Co, New Jersey, USA, 1983.

MRUD, Iranian National Buliding Regulation (Persian). Ministry of Road & Urban Development document. 2009. Available from: http://nezammohandesi.ir/Portals/0/Pdf/Mogharrat-Melli/18.pdf

Adobe Audition CS5.5 help. The Adobe Systems, Inc, 2011.

WHO. STRATEGIES FOR NOISE SURVEYS. World Health Organization. Available from: http://www.who.int/occupational_health/publications/noise7.pdf

ISO. Acoustics-Determination of occupational noise exposure, Engineering method. International Standard Organization ISO 9612.2009.

Files
IssueVol 6 No 1 (2014) QRcode
SectionOriginal Article(s)
Published2015-10-11
Keywords
Data Centers Acoustic Noise Noise Criteria Measurement

Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
How to Cite
1.
JALILZADEH SZ, ASGARI M, SADEGHI ME. A Quantitative Noise Survey in a General Room–Based Data Center. Int J Occup Hyg. 2015;6(1):16-22.